FSP/Fortron
Galleon 1K Rack 1000VA UPS

FSP/Fortron Galleon 1K Rack 1000VAUPS

Varenr: PPF8000200
Lagerstatus: Forventet 29.12.2016
Frakt: 89,- Sjekk din fraktpris
Frakt
Fyll inn postnummer og klikk
knappen for å vise fraktpriser
  Vis priser
5 996,-  inkl. mva
Fra 200,-/mnd (64 mnd)
Utsett betalingen i 4-6 mnd
Velg finansiering i kassen
Kjøp
Produktinfo

GALLEON 1K


The Galleon UPS provides high density, double-conversion on-line power protection. It is ideal for servers, networks applications, as well as for industrial applications.

  • True double-conversion
  • Wide input voltage range (110-300 VAC)
  • Input power factor correction 0.98
  • Output Power Factor 0.8
  • 50Hz/60Hz frequency converter mode
  • Programmable power management outlets
  • Emergency power off function (EPO)
  • Eco mode operation for energy saving (ECO)
  • Generator compatible
  • Charger capacity expansion to 8A for long-run models
  • SNMP+USB+RS-232 multiple communications
  • Smart battery charger design for optimized battery performance
  • Selectable output voltage: 208-240VAC, 110-127VAC
  • Optional rackmount form factor
  • Accessory: External maintenance bypass switch & SNMP card
  • Optional hotswap battery module
  • Bypass function setting for ECO mode or battery failure
  • Other cable accessory can be made by customer’s request

Specifications
Model Galleon 1K (L)
Capacity 1000 VA/ 800W
Input/ Voltage 110/ 120 VAC or 220/ 230/ 240 VAC
Input/ Voltage Range 110-300 VAC ±5%
Input/ Frequence 40Hz ~ 70Hz
Output/ Voltage ± 3% (Batt. Mode)
Output/ Frequence Range 47.5 Hz ~ 52.5 Hz or 57Hz ~ 63 Hz (Synchronized Range)/ 50 Hz ±0.25 Hz or 60 Hz ±0.3 Hz (Batt. Mode)
Output/ Transfer Time(Typical) 4ms (Inverter to Bypass)
Output/ Waveform(Batt. Mode) Pure Sinewave
Battery/ Battery Type & Number 12 V/ 7 Ah, 6
Battery/ Typical Recharge Time 4 hours recover to 90% capacity
Indicators/ Ac Mode V
Indicators/ Battery Mode V
Indicators/ Fault V
Protection/ Full Protection Overload, discharge, overcharge protection
Alarm/ Battery Mode Sounding every 4 seconds
Alarm/ Low Battery Sounding every second
Alarm/ Overload Sounding twice every second
Alarm/ Fault Continuously sounding
Physical/ Dimension, D x W x H (mm) Tower Case: 421 x 190 x 318/ Rack Case: 580 x 438 x 133(3U)
Physical/ Net Weight (kgs) Tower Case/ Standard Model: 26, Long-run Model: 13 Rack Case/ Standard Model: 31, Long-run Model: 22
Operating Environment/ Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Operating Environment/ Noise Level Less than 45dB @ 1 Meter
Management/ Optional USB/ RS-232 Port Supports Windows® 98/2000/2003/XP/Vista/2008, Linux, and MAC