Produktinfo

5130 UPS

  • Protects connected equipment from five of the most common power anomalies: failures, surges, sags, under-voltage and over-voltage
  • Provides more real wattage in less space with a 0.9 power factor—to protect more equipment and leave more room to expand IT systems
  • Offers the choice of rackmount or tower installation—with space-saving 2U or 3U reduced-depth packages, including internal batteries
  • Enables prioritized shutdown of non-essential equipment during outages to maximize battery runtime for critical devices—with load segments
  • Maximizes availability with extended battery runtime options, hot-swappable batteries, optional maintenance bypass, remote monitoring and power management software
  • Provides investment protection with a two-year limited factory warranty, an extended warranty, Flex and PowerTrust service contracts, and a $150,000 load protection guarantee (US and Canada)

General
LEDs 13 status-indicating LEDs
Topology Line interactive
Diagnostics Full system self-test at power up
Transfer Time 1–4 ms typical
ROO/RPO Rear deck emergency stop connector (for remote on/off and power off)
Rail Kit/Tower Stand Included with all units
Electrical Input
Nominal Voltage 120/230 Vac
Voltage Range 120V: 89–151 Vac
230V: 160–294V
(* The high and low thresholds can be user adjusted using the downloadable UPS Configuration tool)
Frequency 50/60 Hz
Frequency Range 47–70 Hz for 50 Hz operation
56.5–70 Hz for 60 Hz operation
Power Draw of UPS (full load) 1250: 10.4A @120V, 5.4A @230V
1750: 14.6A @120V, 7.6A @230V
2500: 20.8A @120V, 10.9A @230V
3000: 25.4A @120V, 14.4 @ 208, 13.0A @230V
Electrical Output
Power Factor 0.9
On Utility Voltage Regulation 120V: 102–132 Vac
230V: 184–265 Vac
On Battery Voltage Regulation -10%, +6% of nominal
Efficiency Normal or line mode: >94%
On battery: 70% (1250–1750 VA), 75% (2500–3000 VA)
Frequency Regulation 0.1 Hz
Over Current Protection Electronic current limit
Load Crest Factor 3:1
Load Segments Two individually controlled output receptacles
Battery
Internal Battery Type 1250/2500 VA: 12V/7.2 Ah; sealed, lead-acid; maintenance free
1750/3000 VA: 12V/9 Ah; sealed, lead-acid; maintenance free
EBM Battery Type 12V/9 Ah
Battery Runtime 1250 VA: 5 min w/internal batteries @100% load (0.9 PF)
1750 VA: 3.5 min w/internal batteries @100% load (0.9 PF)
2500–3000 VA: 3 min w/internal batteries @100% load (0.9 PF)
Battery Replacement Hot-swappable internal batteries
Start-On-Battery Allows start of UPS without utility input
Communications
Serial Port RS-232 (RJ45) ports
USB Port As standard (HID)
Optional Communications Slots ConnectUPS-MS network management card and ModBus
Cables RS-232 and USB 6-foot communications cables included
Power Management Software Eaton Software Suite CD-ROM (bundled with UPS)
Environmental
Safety Markings 120V: UL; cUL
230V: C-Tick; CE, TUV, cUL, UL
Safety Conformance 120V: UL 1778; UL497A; cUL (CAN/CSA C22.2, No. 107.1)
230V: UL1778, UL 497A (data line only); cUL (CAN/CSA C22.2, No. 107.1); EN 50091-1-1 and IEC 60950
EMC Compliance 120V: FCC Part 15 subpart B Class A
230V: EN 50091-2. FCC Part 15 subpart J Class A
Operating Temperature 1250 VA: 0˚C (32˚F) to +40˚C (104˚F)
1750–3000 VA: 0˚C (32˚F) to +35°C (95˚F)
Storage Temperature -15˚C (5˚F) to +50˚C (122˚F)
Relative Humidity 20–95% non-condensing
Surge Suppression ANSI C62.41 Category A (formerly IEEE 587)
Audible Noise Max 45 dBA
Altitude Up to 10,000 ft (3000M) without de-rating